About the Voltage Drop Calculator (NEC)
Electricians, engineers, solar installers, and maintenance teams use a voltage drop calculator to estimate conductor loss before pulling wire or troubleshooting long runs. Enter voltage, phase, current, distance, conductor material, and wire size to calculate volts lost and percentage drop. It supports NEC-informed design decisions for feeders, branch circuits, motors, and low-voltage equipment.
How it works
- Enter source voltage, load current, circuit length, and phase type.
- Select copper or aluminum and the conductor size.
- Calculate voltage drop in volts and as a percentage.
- Compare the result with project limits and NEC informational note guidance.
- Confirm ampacity, terminals, temperature rating, and overcurrent protection separately.
Frequently asked questions
What voltage drop does the NEC recommend?
NEC informational notes commonly reference a maximum 3% drop for branch circuits and 5% total for feeders plus branch circuits for reasonable efficiency. Informational notes are guidance unless adopted by a specification or local rule.
Is voltage drop the same as conductor ampacity?
No. Ampacity is the safe current-carrying capacity of a conductor, while voltage drop is performance loss over distance. A conductor can be code-compliant for ampacity but still have excessive voltage drop.
Why does circuit length matter so much?
Longer conductors have more resistance, so voltage drop increases with distance and current. Single-phase calculations include the full circuit path, while three-phase formulas use the appropriate phase relationship.
Can I fix voltage drop by increasing breaker size?
No. A larger breaker does not reduce conductor resistance and may create an unsafe or noncompliant installation. Use larger conductors, shorter runs, adjusted voltage, or redesigned loads where appropriate.
Does the calculator replace NEC conductor sizing?
No. Final design must also check ampacity, correction factors, terminal ratings, grounding, conduit fill, equipment instructions, and local code adoption.
References
- NFPA 70 National Electrical Code Articles 210 and 215 Informational Notes — voltage drop recommendations
- NFPA 70 National Electrical Code Chapter 9 Table 8 — conductor properties and circular mil areas
- NFPA 70 National Electrical Code Article 310 — conductor ampacity rules